can be reset by setting the
Clear accum. breaking curr
setting to true in the clear menu
from LHMI.
Alarm limit check
The
IACCALM
alarm is activated when the accumulated energy exceeds the value set
with the
AccCurrAlmLvl
threshold setting. However, when the energy exceeds the limit
value set with the
AccCurrLO
threshold setting, the
IACCLOAL
output is activated.
The
IACCALM
and
IACCLOAL
outputs can be blocked by activating the binary input
BLOCK
.
12.17.7.6
Remaining life of the circuit breaker
Every time the breaker operates, the life of the circuit breaker reduces due to wearing.
The wearing in the breaker depends on the tripping current, and the remaining life of
the breaker is estimated from the circuit breaker trip curve provided by the
manufacturer. The remaining life is decremented at least with one when the circuit
breaker is opened.
The operation of the remaining life of the circuit breaker subfunction can be described
by using a module diagram. All the modules in the diagram are explained in the next
sections.
CB life
estimator
POSCLOSE
CBCNTRST
BLOCK
Alarm limit
check
CBLIFEAL
BLK_ALM
I3P
I_A
I_B
I_C
GUID-1565CD41-3ABF-4DE7-AF68-51623380DF29-ANSI V1 EN
Figure 135:
Functional module diagram for estimating the life of the circuit breaker
Circuit breaker life estimator
The circuit breaker life estimator module calculates the remaining life of the circuit
breaker. If the tripping current is less than the rated operating current set with the
RatedOpCurr
setting, the remaining operation of the breaker reduces by one operation.
If the tripping current is more than the rated fault current set with the
RatedFaultCurr
setting, the possible operations are zero. The remaining life due to the tripping current
in between these two values is calculated based on the trip curve given by the
manufacturer. The
OpNumRatCurr
and
OPNumFaultCurr
parameters set the number
1MRK 505 277-UUS C
Section 12
Monitoring
329
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...