Magnitude dead-band supervision
If a measuring value is changed, compared to the last reported value, and the change is
larger than the ±ΔY pre-defined limits that are set by user (
XZeroDb
), then the
measuring channel reports the new value to a higher level, if this is detected by a new
measured value. This limits the information flow to a minimum necessary. Figure
shows an example with the magnitude dead-band supervision. The picture is
simplified: the process is not continuous but the values are evaluated with a time
interval of one execution cycle from each other.
99000529.vsd
Y
t
Value Reported
(1st)
Value Reported
Value Reported
Y1
Y2
Y3
D
Y
D
Y
D
Y
D
Y
D
Y
D
Y
Value Reported
IEC99000529 V1 EN
Figure 105:
Magnitude dead-band supervision reporting
After the new value is reported, the ±ΔY limits for dead-band are automatically set
around it. The new value is reported only if the measured quantity changes more than
defined by the ±ΔY set limits.
Integral dead-band reporting
The measured value is reported if the time integral of all changes exceeds the pre-set
limit (
XDbRepInt
, where an example of reporting with integral dead-band
supervision is shown. The picture is simplified: the process is not continuous but the
values are evaluated with a time interval of one execution cycle from each other.
The last value reported, Y1 in figure
serves as a basic value for further
measurement. A difference is calculated between the last reported and the newly
measured value and is multiplied by the time increment (discrete integral). The
Section 12
1MRK 505 277-UUS C
Monitoring
240
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...