Name
Values (Range)
Unit
Step
Default
Description
t1Min
0.000 - 60.000
s
0.001
5.000
Minimum operate time for inverse curves for
step 1
TD1
0.05 - 1.10
-
0.01
0.05
Time multiplier for the inverse time delay for
step 1
OperationStep2
Disabled
Enabled
-
-
Enabled
Enable execution of step 2
OpMode2
1 out of 3
2 out of 3
3 out of 3
-
-
1 out of 3
Number of phases required to operate (1 of 3,
2 of 3, 3 of 3) from step 2
Pickup2
1 - 100
%VB
1
50
Voltage start value (DT & IDMT) in % of
VBase for step 2
t2
0.000 - 60.000
s
0.001
5.000
Definie time delay of step 2
Table 68:
UV2PTUV (27) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 6
-
1
1
Selection of one of the Global Base Value
groups
ConnType
PhN DFT
PhN RMS
PhPh DFT
PhPh RMS
-
-
PhN DFT
Group selector for connection type
8.1.6
Monitored data
Table 69:
UV2PTUV (27) Monitored data
Name
Type
Values (Range)
Unit
Description
V_A
REAL
-
kV
Voltage in phase A
V_B
REAL
-
kV
Voltage in phase B
V_C
REAL
-
kV
Voltage in phase C
8.1.7
Operation principle
Two-step undervoltage protection (UV2PTUV ,27) is used to detect low power system
voltage. UV2PTUV (27) has two voltage measuring steps with separate time delays. If
one, two or three phase voltages decrease below the set value, a corresponding
PICKUP signal is generated. UV2PTUV (27) can be set to PICKUP/TRIP based on
1
out of 3
,
2 out of 3
or
3 out of 3
of the measured voltages, being below the set point. If
the voltage remains below the set value for a time period corresponding to the chosen
time delay, the corresponding trip signal is issued. The time delay characteristic is
1MRK 505 277-UUS C
Section 8
Voltage protection
125
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...