Voltage polarizing
When voltage polarizing is selected the protection will use either the residual voltage
3V
0
or the negative sequence voltage V
2
as polarizing quantity V3P.
The residual voltage can be:
1. directly measured (when a dedicated VT input of the IED is connected in PCM600
to the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input V3P). This dedicated IED VT input shall be then connected to
open delta winding of a three phase main VT.
2. calculated from three phase voltage input within the IED (when the fourth analog
input into the pre-processing block connected to EF4PTOC (51N/67N) analog
function input V3P is NOT connected to a dedicated VT input of the IED in
PCM600). In such case the pre-processing block will calculate 3V
0
from the first
three inputs into the pre-processing block by using the following formula:
VPol=3V0=(VA +VB +VC)
ANSIEQUATION2407 V1 EN
(Equation 9)
where:
VA, VB, VC
are fundamental frequency phasors of three individual phase voltages.
In order to use this, all three phase-to-ground voltages must be connected to three IED
VT inputs.
The residual voltage is pre-processed by a discrete fourier filter. Thus, the phasor of the
fundamental frequency component of the residual voltage is derived.
The negative sequence voltage is calculated from the three-phase voltage input within
the IED by using the pre-processing block. The preprocessing block will calculate the
negative sequence voltage from the three inputs into the pre-processing block by using
the following formula:
(
)/3
VPol VA alpha VB alpha VC
=
+
× +
×
GUID-F09A69D7-A8A6-4354-B0B8-F4EC7BBE603F V2 EN
(Equation 10)
where:
VA, VB, VC
are fundamental frequency phasors of three individual phase voltages.
alpha
unit phasor with an angle of 120 degrees.
Section 7
1MRK 505 277-UUS C
Current protection
90
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...