A
1L
A
F
A
V
p Z
I
R I
= ×
× +
×
EQUATION1603 V1 EN
(Equation 71)
Where:
I
A
is according to table
The accuracy of the distance-to-fault calculation, using the non-compensated
impedance model, is influenced by the pre-fault load current. So, this method is only
used if the load compensated models do not function.
12.13.8
Technical data
Table 249:
LMBRFLO technical data
Function
Value or range
Accuracy
Reactive and resistive reach
(0.001-1500.000) Ω/phase
± 2.0% static accuracy
± 2.0% degrees static angular
accuracy
Conditions:
Voltage range: (0.1-1.1) x V
n
Current range: (0.5-30) x I
n
Phase selection
According to input signals
-
Maximum number of fault
locations
100
-
12.14
Station battery supervision SPVNZBAT
12.14.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Station battery supervision function
SPVNZBAT
U<>
-
Section 12
1MRK 505 277-UUS C
Monitoring
308
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...