The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a
cross to receive the integer values.
The implementation for IEC61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
14.7
GOOSE function block to receive a measurand value
GOOSEMVRCV
14.7.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV
-
-
14.7.2
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
14.7.3
Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 155:
GOOSEMVRCV function block
Section 14
1MRK 505 277-UUS C
Station communication
366
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...