15.3.3.3
Signals
Table 332:
ACTVGRP Input signals
Name
Type
Default
Description
ACTGRP1
BOOLEAN
0
Selects setting group 1 as active
ACTGRP2
BOOLEAN
0
Selects setting group 2 as active
ACTGRP3
BOOLEAN
0
Selects setting group 3 as active
ACTGRP4
BOOLEAN
0
Selects setting group 4 as active
Table 333:
ACTVGRP Output signals
Name
Type
Description
GRP1
BOOLEAN
Setting group 1 is active
GRP2
BOOLEAN
Setting group 2 is active
GRP3
BOOLEAN
Setting group 3 is active
GRP4
BOOLEAN
Setting group 4 is active
GRP_CHGD
BOOLEAN
Pulse when setting changed
15.3.3.4
Settings
The function does not have any settings available in Local HMI or Protection and
Control IED Manager (PCM600).
15.3.4
Operation principle
Parameter setting groups (ACTVGRP) function has four functional inputs, each
corresponding to one of the setting groups stored in the IED. Activation of any of these
inputs changes the active setting group. Five functional output signals are available for
configuration purposes, so that up to date information on the active setting group is
always available.
A setting group is selected by using the local HMI, from a front connected personal
computer, remotely from the station control or station monitoring system or by
activating the corresponding input to the ACTVGRP function block.
Each input of the function block can be configured to connect to any of the binary
inputs in the IED. To do this PCM600 must be used.
The external control signals are used for activating a suitable setting group when
adaptive functionality is necessary. Input signals that should activate setting groups
must be either permanent or a pulse exceeding 400 ms.
Section 15
1MRK 505 277-UUS C
Basic IED functions
390
Technical Manual
Summary of Contents for REB650
Page 1: ...Relion 650 series Busbar protection REB650 ANSI Technical Manual ...
Page 2: ......
Page 34: ...28 ...
Page 52: ...46 ...
Page 128: ...122 ...
Page 150: ...144 ...
Page 192: ...186 ...
Page 222: ...216 ...
Page 360: ...354 ...
Page 378: ...372 ...
Page 437: ...IEC12000585 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 431 Technical Manual ...
Page 438: ...IEC12000586 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 432 Technical Manual ...
Page 439: ...IEC12000587 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 433 Technical Manual ...
Page 440: ...IEC12000588 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 434 Technical Manual ...
Page 441: ...IEC12000589 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 435 Technical Manual ...
Page 442: ...IEC12000590 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 436 Technical Manual ...
Page 443: ...IEC12000591 V1 EN 1MRK 505 277 UUS C Section 16 IED physical connections 437 Technical Manual ...
Page 444: ...IEC12000592 V1 EN Section 16 1MRK 505 277 UUS C IED physical connections 438 Technical Manual ...
Page 454: ...448 ...
Page 503: ...497 ...