5 Calibration, M2000
5.3.9 Updating the revolution counters
128
3HAC021111-001 Revision: B
4.
Select the desired unit and
choose
Rev Counter
Update
from the
Calib
menu.
The Revolution Counter
Update window appears.
xx0100000202
5.
Select the desired axis and
press
Incl
to include it (it
will be marked with an x) or
press
All
to select all
axes.
6.
Press
OK
when all axes
that are to be updated are
marked with an x.
CANCEL
returns to the Cal-
ibration window.
7.
Press
OK
again to confirm
and start the update.
CANCEL
returns to the
Revolution Counter Update
window.
8.
At this point, it is recom-
mended that the revolution
counter values are saved to
a diskette.
Not required.
9.
Recheck the calibration
position.
Detailed in section Checking the calibration position
on page 105.
Step
Action
Illustration
Summary of Contents for IRB 1400
Page 1: ...Product manual Articulated robot IRB 1400 M2004 ...
Page 2: ......
Page 3: ...Product manual 3HAC021111 001 Revision B Articulated robot IRB 1400 M2000 M2004 ...
Page 12: ...0 0 2 Product documentation M2000 10 3HAC021111 001 Revision B ...
Page 132: ...5 Calibration M2000 5 4 1 Post calibration procedure 130 3HAC021111 001 Revision B ...
Page 142: ......
Page 148: ...7 Alternative calibration 7 0 5 Retrieving offset values 146 3HAC021111 001 Revision B ...
Page 170: ...10 Foldouts 10 0 1 Introduction 168 3HAC021111 001 Revision B ...
Page 171: ......
Page 172: ......
Page 173: ......
Page 174: ......
Page 175: ......
Page 176: ......
Page 177: ......
Page 178: ......
Page 179: ......
Page 180: ......
Page 182: ...11 Circuit diagram 11 0 1 Introduction 170 3HAC021111 001 Revision B ...
Page 196: ...Index 184 ...
Page 197: ......