5 Calibration, M2000
5.3.7 Fine calibration procedure on TPU
3HAC021111-001 Revision: B
123
4.
Select the desired unit and
choose
Fine Cali-
brate
from the
Calib
menu. A Warning window
appears.
xx0100000203
5.
Move the desired robot
axis according to the cali-
bration procedure for cur-
rent axis. These
procedures are found in
section Calibration on
page 110.
Press OK. The Fine Cali-
brate window appears.
xx0100000204
6.
Select the desired axis
and press
Incl
to
include it (it will be marked
with an x) or press
All
to
select all axes.
7.
Press
OK
when all axes
that are to be updated are
marked with an x.
CANCEL
returns to the
Calibration window.
8.
Press
OK
again to con-
firm and start the update.
CANCEL
returns to the
Fine Calibration window.
An alert box is displayed
during calibration. The
Status window appears
when the fine calibration is
complete. The revolution
counters are always
updated at the same time
as the calibration is per-
formed.
Step
Action
Note/Illustration
Summary of Contents for IRB 1400
Page 1: ...Product manual Articulated robot IRB 1400 M2004 ...
Page 2: ......
Page 3: ...Product manual 3HAC021111 001 Revision B Articulated robot IRB 1400 M2000 M2004 ...
Page 12: ...0 0 2 Product documentation M2000 10 3HAC021111 001 Revision B ...
Page 132: ...5 Calibration M2000 5 4 1 Post calibration procedure 130 3HAC021111 001 Revision B ...
Page 142: ......
Page 148: ...7 Alternative calibration 7 0 5 Retrieving offset values 146 3HAC021111 001 Revision B ...
Page 170: ...10 Foldouts 10 0 1 Introduction 168 3HAC021111 001 Revision B ...
Page 171: ......
Page 172: ......
Page 173: ......
Page 174: ......
Page 175: ......
Page 176: ......
Page 177: ......
Page 178: ......
Page 179: ......
Page 180: ......
Page 182: ...11 Circuit diagram 11 0 1 Introduction 170 3HAC021111 001 Revision B ...
Page 196: ...Index 184 ...
Page 197: ......