7.4.2.1.2.3.1
—
Dependent Parameter
Control value
Options:
0…100
This parameter is used to specify the control value that is to apply after bus voltage recovery until a
new control value is received.
7.4.2.1.2.4
Reaction on bus voltage recovery Fan output
This parameter is only visible for:
•
FCC/S 1.1.1.1
•
FCC/S 1.1.2.1
•
FCC/S 1.2.1.1
•
FCC/S 1.2.2.1
•
FCC/S 1.4.1.1
Options:
Unchanged
Applies control value
1
2
3
This parameter is used to specify the fan speed that is to apply after bus voltage recovery.
•
Unchanged
: The same fan speed as before/during the bus voltage failure applies. The status of
the automatic mode also remains unchanged. The fan follows the valve control value if the au-
tomatic mode is active.
•
Applies control value
: The speed is dependent on the valve control value. The automatic mode
is active. If the automatic mode was deactivated before the download, it is activated.
•
1
: The fan runs with speed 1 in the manual mode.
•
2
: The fan runs with speed 2 in the manual mode.
•
3
: The fan runs with speed 3 in the manual mode.
Note
The
Applies control value
option is only available if it has not been deactivated in the
Enable
automatic mode based on control value
parameter in the
Fan output
window.