ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 244
7.7.2.1.5.1
—
Dependent Parameter
Time interval for cyclical monitoring
Options:
00:00:30…00:05:00…18:12:15
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the
Error: fill level status receipt
group object is changed to alarm and the controller
reacts as if the fill level alarm were active. This means that the controller sets the control value for
cooling to 0. As long as the dew point alarm is active, this control value for cooling cannot be
raised again. This state remains active until a new value is received in the group object monitored
that clears the alarm.
Note
If the device is changed to the heating mode (on a device that is used for heating and cooling),
the device continues to function as before, without the alarm having any effect, because the
alarm only relates to cooling.
For more information on the fill level, see .
7.7.2.1.6
—
Dependent Parameter
Monitor receipt of group object "Toggle heating/cooling"
The parameter is only visible if in the
Heating/Cooling changeover
parameter in the
Application
parameters
parameter window, the
Via object only
or
Via object and automatically
option has been
selected.
Options:
Deactivated
Activated
The monitoring of the
Heating/Cooling changeover
group object is enabled using this parameter.
The change in the type of operation can be monitored using this parameter.
•
Deactivated
: The monitoring of the
Heating/Cooling changeover
group object is deactivated.
•
Activated
: The monitoring of the group object is active. The dependent parameters
Time
interval for cyclical monitoring
and
Heating/cooling mode when monitoring time exceeded
as
well as the
Error: heating/cooling receipt
group object are enabled.
7.7.2.1.6.1
—
Dependent Parameter
Time interval for cyclical monitoring
Options:
00:00:30…00:05:00…18:12:15
The monitoring time within which the group object must be received is specified using this parame-
ter. Otherwise the
Error: heating/cooling receipt
alarm object is changed to alarm and the value set
in the
Heating/cooling mode when monitoring time exceeded
parameter applies.