ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 221
7.6.3
Comfort heating setpoint = Comfort cooling setpoint
This parameter is enabled if the controller has been parameterized both for heating and for cool-
ing. For this purpose,
Deactivated
must not be selected for the parameters
Basic-stage heating
and
Basic-stage cooling
in the
Application parameters
parameter window.
Options:
No
Yes
This parameter defines how the comfort values for heating and cooling depend on each other.
•
No
: Two separate comfort setpoints are used for heating and cooling. The related active set-
point is output via the
Current setpoint
object. The changeover between heating and cooling is
undertaken using the method defined in the
Application parameters
parameter window in the
Heating/Cooling changeover
parameter. On the selection of the
Automatically
option, the
changeover between heating and cooling is dependent on the absolute temperatures set for
Comfort heating/cooling.
•
Yes
: The device has one and the same setpoint for heating and cooling in the Comfort mode.
The changeover to heating takes place on dropping below the setpoint minus the hysteresis.
The changeover to cooling takes place on exceeding the setpoint plus the hysteresis. The hys-
teresis is parameterizable. The
Comfort heating setpoint
and
Comfort cooling setpoint
parame-
ters are replaced by the
Setpoint for Comfort heating and cooling
parameter. In addition, the
Hysteresis for Toggle heating/cooling
parameter is displayed.
7.6.3.1
Selection of No
7.6.3.1.1
—
Dependent Parameter
Comfort heating setpoint
This parameter is only visible if the
Deactivated
option has not been selected for the
Basic-stage
heating
parameter in the
Application parameters
parameter window, and the
No
option has been
selected for the
Comfort heating setpoint = Comfort cooling setpoint
parameter.
Options:
10…21…40
This value defines the setpoint for the heating comfort temperature. If the device is in the type of
operation heating and is changed to the Comfort operating mode, the device regulates to this tem-
perature.
7.6.3.1.2
—
Dependent Parameter
Comfort cooling setpoint
This parameter is only visible if the
Deactivated
option has not been selected for the
Basic-stage
cooling
parameter in the
Application parameters
parameter window, and the
No
option has been
selected for the
Comfort heating setpoint = Comfort cooling setpoint
parameter.
Options:
10…25…40
This value defines the setpoint for the comfort cooling temperature. If the device is the type of op-
eration cooling and is changed to the Comfort operating mode, the device regulates to this temper-
ature.