ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 252
7.8.1.1.1.3.2
—
Dependent Parameter
Open if control value greater than or equal to
Options:
1…100
The output switches ON continuously if the value parameterized here is greater than or equal to
the received control value. If a control value less than the parameterized value is received, the out-
put switches OFF.
7.8.1.1.1.3.3
—
Dependent Parameter
Valve drive opening/closing time
This parameter is visible if, in the
Valve output
parameter, the
Thermoelectric (PWM)
or
Open/
Close signal
option has been selected.
Options:
10…60…900
With this parameter, a time is set in seconds that the connected valve requires to move from posi-
tion 0 % (valve closed) to position 100 % (valve fully open), or the valve requires to move from
100 % to 0 %.
Note
The time should be taken from the technical data of the valve, and it corresponds with the total
runtime.
7.8.1.1.2
Send status values
Options:
On request
On change
Cyclically
After a change or on request
After a change or request and cyclically
This parameter defines when the valve output status value are to be sent. It affects the group ob-
jects
Status byte valve A
,
Fault: valve output A
and
Status Control value
for the valve drive.
•
On request
: The valve output status values are sent on the receipt of a command via the
Request status values
group object.
•
On change
: The values are sent on a change in the object values (e.g. change from 0 to 1).
With the
Status Control value
group object the values are only sent if the change in the control
value is at least 1 %.
•
Cyclically
: If this option is selected, the status values are sent automatically after an adjustable
time has elapsed. The
Every
dependent parameter is displayed.
•
After a change or request
: The values are sent on request and on a change.
•
After a change or request and cyclically
: The values are sent on request and on a change and
cyclically. The
Every
dependent parameter is displayed.
7.8.1.1.2.1
—
Dependent Parameter
Every
Options:
00:00:30…00:05:00…18:12:15
This parameter is used to set the time after which the status values are to be sent cyclically. The
group objects are sent after each cycle.