ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 222
7.6.3.2
Selection of Yes
7.6.3.2.1
—
Dependent Parameter
Hysteresis for Toggle heating/cooling
This parameter is only visible if the
Yes
option has been selected for the
Comfort heating setpoint
= Comfort cooling setpoint
parameter.
Options:
00.5…02.0…10.0
The parameter defines the hysteresis for the changeover between heating and cooling. If the room
temperature exceeds the setpoint temperature plus hysteresis, the changeover is to cooling. If the
room temperature drops below the setpoint temperature minus hysteresis, the changeover is to
heating.
Note
A change between heating and cooling is only possible in the Comfort mode.
7.6.3.2.2
—
Dependent Parameter
Setpoint for Comfort heating and cooling
This parameter is only visible if the
Yes
option has been selected for the
Comfort heating setpoint
= Comfort cooling setpoint
parameter.
Options:
10…21…40
This value defines the setpoint for the comfort temperature for heating and cooling. If the operating
mode is changed to Comfort, the device regulates to this temperature in both types of operation
heating and cooling.