ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 321
No.
Function
Name
Data Point Type
(DPT)
Length
Flags
C
R
W T
U
101
Request fan manually (slave)
Channel – Actuator
1.001
1 bit
X
X
101
Request fan manually (master)
Channel – Controller 1.001
1 bit
X
X
102
Confirm fan manually (slave)
Channel – Actuator
1.001
1 bit
X
X
X
102
Confirm fan manually (master)
Channel – Controller 1.001
1 bit
X
X
103
Request fan speed (master)
Channel – Controller 5.010
1 byte
X
X
103
Request fan speed (master)
Channel – Controller 5.001
1 byte
X
X
103
Request fan speed (slave)
Channel – Actuator
5.010
1 byte
X
X
103
Request fan speed (slave)
Channel – Actuator
5.001
1 byte
X
X
104
Confirm fan speed (master)
Channel – Controller 5.010
1 byte
X
X
X
104
Confirm fan speed (master)
Channel – Controller 5.001
1 byte
X
X
X
105
Controller RHCC status
Channel – Controller 22.101
2 bytes
X
X
X
106
Controller HVAC status (master)
Channel – Controller 5.001
1 byte
X
X
X
107
Current HVAC operating mode
Channel – Controller 20.102
1 byte
X
X
X
108
Comfort heating setpoint
Channel – Controller 9.001
2 bytes
X
X
108
Setpoint for Comfort heating and cooling
Channel – Controller 9.001
2 bytes
X
X
109
Comfort cooling setpoint
Channel – Controller 9.001
2 bytes
X
X
110
Economy heating setpoint
Channel – Controller 9.001
2 bytes
X
X
111
Economy cooling setpoint
Channel – Controller 9.001
2 bytes
X
X
112
Standby heating setpoint
Channel – Controller 9.001
2 bytes
X
X
113
Standby cooling setpoint
Channel – Controller 9.001
2 bytes
X
X
114
Building protection heating setpoint
Channel – Controller 9.001
2 bytes
X
X
115
Building Protection cooling setpoint
Channel – Controller 9.001
2 bytes
X
X
116
Heating control value
Channel – Actuator
5.001
1 byte
X
X
X
X
117
Cooling control value
Channel – Actuator
5.001
1 byte
X
X
X
X
118
Basic-stage heating limit temperature
Channel – Controller 9.001
2 bytes
X
X
X
X
119
Additional-stage heating limit temperature
Channel – Controller 9.001
2 bytes
X
X
X
X
120
Basic-stage cooling limit temperature
Channel – Controller 9.001
2 bytes
X
X
X
X
121
Additional-stage cooling limit temperature
Channel – Controller 9.001
2 bytes
X
X
X
X
Table 34: Group objects – overview