ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 250
7.8.1.1.1.2
Selection of Motor-driven (3-point)
7.8.1.1.1.2.1
—
Dependent Parameter
Reversing time
Options:
50…500…1,000
This parameter defines the reversing delay time of the valve drive.
Note
The technical data for the valve drive must be observed.
7.8.1.1.1.2.2
—
Dependent Parameter
Switch on time for valve drive from 0 to 100 %
Options:
10…120…6,000
This parameter sets the time that the output switches on to move the valve drive or the valve from
0 % (closed) to position 100 % (fully opened).
Note
The time required should be taken from the technical data of the valve.
7.8.1.1.1.2.3
—
Dependent Parameter
Automatic adjustment of valve drive
Options:
No
Yes
If the control value 0% is only rarely achieved in ongoing operation, this can lead to inaccuracies in
positioning control. This parameter activates automatic adjustment to move the valve drive in a de-
fined manner to the 0% position. This serves as the basis for position adjustment.
•
Yes
: Automatic adjustment is activated. The dependent parameter
Number of changes until
adjustment
is displayed.
•
No
: Automatic adjustment is deactivated.