ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 188
7.5.1.7.1.2.5.2
—
Dependent Parameter
Control value difference for sending control value
This parameter is only visible on the selection of the
PI continuous (0…100 %)
or
PI continuous
(0...100 %) for Fan Coil
option.
Options:
2 %
5 %
10 %
Only send cyclically
The control values for the PI continuous controller 0…100 % are not sent after each calculation,
but when there is a difference in the calculation compared to the last value sent and sending is ap-
propriate. This value difference can be entered here.
7.5.1.7.1.2.5.3
—
Dependent Parameter
Send control value cyclically (0 = cyclical sending disabled)
This parameter is only visible on the selection of the
PI continuous (0…100 %)
or
PI continuous
(0...100 %) for Fan Coil
option.
Options:
0…15…60
This parameter is used to specify the cycle time with which the control value is to be sent.
On the selection of the value 0, cyclic sending is deactivated.
Note
If the control value is only output via a group object, this value should not be set to 0 because
otherwise it will not be ensured that the actuator receives its control value.
In particular, in combination with the
Control value difference for sending control value
parameter
and the
Only send cyclically
option that can be selected there, the value 0 is not allowed to be se-
lected. This configuration would mean that the control value is never output.