ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 295
7.12.1.1.5
—
Dependent Parameter
Manual setpoint adjustment via KNX with
This parameter is only displayed if you select
No
when setting
Connect analog room control unit to
physical device input a
.
Options:
DPT 6.010 (meter pulses)
DPT 9.001 (absolute temperature value)
DPT 9.002 (relative temperature value)
This parameter determines the datapoint type used to adjust the setpoint via group objects
Request setpoint adjustment
and
Confirm setpoint adjustment
.
•
DPT 6.010 (meter pulses)
: This is the only viable option if you are using legacy ABB devices.
•
DPT 9.001 (Absolute temperature value)
: This adjusts the setpoint as an absolute temperature
value by sending the new temperature required. Likewise, the
Confirm setpoint adjustment
group object sends the new temperature as an absolute value.
•
DPT 9.002 (relative temperature value)
: This adjusts the setpoint as a relative temperature
value by sending a target temperature change (e.g. +2 °C). Likewise, the
Confirm setpoint
adjustment
group object sends the new temperature as a relative value.
Note
DPT 9.001 and DPT 9.002 temperature adjustment will not work on legacy ABB devices that do
not yet support the latest version of the master/slave concept. For these devices, DPT 6.010 is
the only option, which means that other equipment (such as display systems) cannot read the
setpoint adjustment.
However, they can read or display the current target temperature via the
Current setpoint
group
object.
Before adjusting a setpoint with an analog room control unit, please check which setpoint adjust-
ment format the controller supports.
You can also communicate setpoint changes for implementation on other equipment via the
group objects
Base setpoint
,
Comfort heating setpoint
or
Comfort cooling setpoint
.
Caution! Note that changing the base setpoint also changes the Standby and Economy tempera-
tures. To prevent this, use absolute rather than relative setpoint adjustment (
Setpoint manager
–
Setpoint specification and adjustment
). However, note that with both types of adjustment, the
parametrized maximum setpoint increase/reduction limits are no longer taken into account.