Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 304
7.13.1.4.1.1
—
Dependent Parameter
NTC type
Options:
NTC10-01 [-15…+100 C]
NTC10-02 [-15…+100°C]
NTC10-03 [-15…+100°C]
NTC20 [0…+100°C]
This parameter allows you to choose the NTC sensor type that is connected. An NTC10 sensor
has a resistance of 10 kohms at 25 °C. An NTC20 has a resistance of 20 kohms. Individual types
vary in terms of their resistance curves.
7.13.1.4.1.2
—
Dependent Parameter
KTY type
Options:
KT 100 / 110 / 130
KT 210 / 230
KTY 10-5 / 11-5 / 13-5
KTY 10-6 / 10-62 / 11-6 / 13-6 / 16-6 / 19-6
KTY 10-7 / 11-7 / 13-7
KTY 21-5 / 23-5
KTY 21-6 / 23-6
KTY 21-7 / 23-7
KTY 81-110 / 81-120 / 81-150
KTY 82-110 / 82-120 / 82-150
KTY 81-121 / 82-121
KTY 81-122 / 82-122
KTY 81-151 / 82-151
KTY 81-152 / 82-152
KTY 81-210 / 81-220 / 81-250
KTY 82-210 / 82-220 / 82-250
KTY 81-221 / 82-221
KTY 81-222 / 82-222
KTY 81-251 / 82-251
KTY 81-252 / 82-252
KTY 83-110 / 83-120 / 83-150
KTY 83-121
KTY 83-122
KTY 83-151
User-defined
This parameter allows you to select a predefined KTY sensor.
•
User-defined
: This displays the dependent parameters
Resistance in ohms at -20…+120 °C
.
Note
When using a KTY sensor that is not in the list, you can use the
User-defined
option to enter its
characteristic.
To ensure that the analog input works properly with respect to user-defined entries, the resis-
tance values as visible for the preset values must be in ascending order.
An incorrect entry can result in unrealistic output values.