ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 234
7.7.1.1.1.2
—
Dependent Parameter
Fan output / Fan output for forced operation ON / Fan output for forced operation OFF
This parameter only applies to:
•
FCC/S 1.1.1.1
•
FCC/S 1.1.2.1
•
FCC/S 1.2.1.1
•
FCC/S 1.2.2.1
•
FCC/S 1.4.1.1
Options:
Unchanged
Applies control value
1
2
3
This parameter is used to specify the fan speed that is to apply with forced operation active (for 2-
bit in the related state, ON or OFF).
•
Unchanged
: The same fan speed as before the activation of the forced operation applies.
•
Applies control value
: The speed is dependent on the valve control value. The automatic mode
is active.
•
1
: The fan runs at speed 1.
•
2
: The fan runs at speed 2.
•
3
: The fan runs at speed 3.
7.7.1.1.1.3
—
Dependent Parameter
Fan output / Fan output for forced operation ON / Fan output for forced operation OFF
This parameter only applies to:
•
FCC/S 1.3.1.1
•
FCC/S 1.3.1.1
•
FCC/S 1.5.1.1
•
FCC/S 1.5.2.1
Options:
Unchanged
Applies control value
33 %
66 %
100 %
This parameter is used to specify the fan speed that is to apply with forced operation active (for 2-
bit in the related state, ON or OFF).
•
Unchanged
: The same fan speed as before the activation of the forced operation applies.
•
Applies control value
: The speed is dependent on the valve control value. The automatic mode
is active.
•
33 %
: The fan runs at speed 33 %.
•
66 %
: The fan runs at speed 66 %.
•
100 %
: The fan runs at speed 100 %.