ABB i-bus
®
KNX
Group objects
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 352
No.
Function
Group object name Data Type
Flag
109
Comfort cooling setpoint
Channel – Controller 2 bytes
DPT 9.001
C, W
This group object is enabled if the parameter
Setpoint specification and adjustment
is set to
Absolute
and
Comfort heating setpoint = Comfort cooling setpoint
is set to
No
in the
Setpoint manager
parameter window.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Comfort cooling. The value re-
ceived via this group object is permanently stored and serves as the new Comfort cooling setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10…40 °C. A value outside this range is limited to this range.
110
Economy heating setpoint
Channel – Controller 2 bytes
DPT 9.001
C, W
This group object is enabled if the parameter
Setpoint specification and adjustment
in the
Setpoint manager
parameter window is parametrized with
Absolute
.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Economy heating. The value re-
ceived via this group object is permanently stored and serves as the new Economy heating setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10…40 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will
automatically classify it below this value.
111
Economy cooling setpoint
Channel – Controller 2 bytes
DPT 9.001
C, W
This group object is enabled if the parameter
Setpoint specification and adjustment
in the
Setpoint manager
parameter window is parametrized with
Absolute
.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Economy cooling. The value re-
ceived via this group object is permanently stored and serves as the new Economy cooling setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10…40 °C. A value outside this range is limited to this range.
The value must be greater than the value for comfort cooling. If a value is not below this value, the device will
automatically classify it below this value.
112
Standby heating setpoint
Channel – Controller 2 bytes
DPT 9.001
C, W
This group object is enabled if the parameter
Setpoint specification and adjustment
in the
Setpoint manager
parameter window is parametrized with
Absolute
.
This group object is hidden in actuator mode.
This group object can directly influence and overwrite the stored setpoint for Standby heating. The value re-
ceived via this group object is permanently stored and serves as the new Standby heating setpoint. Manual
setpoint adjustment acts on this setpoint.
The value must lie in the valid value range of 10…40 °C. A value outside this range is limited to this range.
The value must be less than the value for comfort heating. If a value is not below this value, the device will
automatically classify it below this value.