98 Electrical installation
Default I/O connection diagram (ABB standard macro)
Terminal sizes:
R0…R3: 0.2…2.5 mm
2
(24…14 AWG) (ter24V, DGND, DCOM, B+, A-, DGND,
Ext. 24V)
0.14…1.5 mm
2
(26…16 AWG) (terminals DI, AI, AO, AGND, RO, STO)
R5…R9: 0.14…2.5 mm
2
(all terminals)
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft)
max.
500 ohm
1…10 kohm
S1
AI1 U/I
Voltage/Current selection for AI1:
1)
S2
AI2 U/I
Voltage/Current selection for AI2:
2)
XI
Reference voltage and analog inputs and outputs
1
SCR
Signal cable shield (screen)
2
AI1
Output frequency/speed reference
: 0…10 V
4)
3
AGND
Analog input circuit common
4
+10V
Reference voltage 10 V DC
5
AI2
Not configured
6
AGND
Analog input circuit common
7
AO1
Output frequency:
0…20 mA
8
AO2
Output current:
0…20 mA
9
AGND
Analog output circuit common
S3
AO1 I/U
Voltage/Current selection for AO1:
X2 & X3
Aux. voltage output and programmable digital inputs
10
+24V
Aux. voltage 24 V DC, max. 250 mA
3)
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Forward (0) / Reverse (1)
15
DI3
Constant frequency/speed selection
5)
16
DI4
Constant frequency/speed selection
5)
17
DI5
Ramp set 1 (0) / Ramp set 2 (1)
6)
18
DI6
Not configured
X6, X7, X8
Relay outputs
19
RO1C
Ready run
250 V AC / 30 V DC
2 A
20
RO1A
21
RO1B
22
RO2C
Running
250 V AC / 30 V DC
2 A
23
RO2A
24
RO2B
25
RO3C
Fault (-1)
250 V AC / 30 V DC
2 A
26
RO3A
27
RO3B
X5
EIA-485 Modbus RTU
29
B+
Embedded Modbus RTU (EIA-485). See
ACS580 firmware manual
(3AXD50000016097
[English]).
30
A-
31
DGND
S4
TERM
Serial data link termination switch
S5
BIAS
Serial data link bias resistors switch
X4
Safe torque off
34
OUT1
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start. See chapter
on page
35
OUT2
36
SGND
37
IN1
38
IN2
X10
24 V AC/DC
40
24 V AC/DC- in R5…R9 only: Ext. 24V AC/DC input to power up the
control board when the main supply is
41
24 V AC/DC+ in
U
I
U
I
U
I
8)
7)
7)
7)
9)
See the notes on
page
.
Summary of Contents for ACS580-01 drives
Page 1: ...ABB general purpose drives Hardware manual ACS580 01 drives 0 75 to 250 kW...
Page 4: ......
Page 11: ...Table of contents 11 Document library on the Internet 225...
Page 12: ...12 Table of contents...
Page 72: ...72 Planning the electrical installation...
Page 79: ...Electrical installation 79 R6 R9 3 3 4...
Page 132: ...132 Maintenance and hardware diagnostics...
Page 168: ...168 Dimension drawings Frame R0 IP21 3AXD10000257110...
Page 169: ...Dimension drawings 169 Frame R0 IP55 3AXD10000341562...
Page 170: ...170 Dimension drawings Frame R1 IP21 3AXD10000257188...
Page 171: ...Dimension drawings 171 Frame R1 IP55 3AXD10000336766...
Page 172: ...172 Dimension drawings Frame R2 IP21 3AXD10000257203...
Page 173: ...Dimension drawings 173 Frame R2 IP55 3AXD10000341578...
Page 174: ...174 Dimension drawings Frame R3 IP21 3AXD10000257219...
Page 175: ...Dimension drawings 175 Frame R3 IP55 3AXD10000335424...
Page 176: ...176 Dimension drawings Frame R4 IP21 3AXD10000332430...
Page 177: ...Dimension drawings 177 Frame R4 IP55 3AXD10000427933...
Page 178: ...178 Dimension drawings Frame R5 IP21 3AXD10000412280...
Page 179: ...Dimension drawings 179 Frame R5 IP55 3AXD10000415964...
Page 180: ...180 Dimension drawings Frame R6 IP21 3AXD10000258705...
Page 181: ...Dimension drawings 181 Frame R6 IP55 3AXD10000330667...
Page 182: ...182 Dimension drawings Frame R7 IP21 3AXD10000258995...
Page 183: ...Dimension drawings 183 Frame R7 IP55 3AXD10000330932...
Page 184: ...184 Dimension drawings Frame R8 IP21 3AXD10000287670...
Page 185: ...Dimension drawings 185 Frame R8 IP55 3AXD10000332446...
Page 186: ...186 Dimension drawings Frame R9 IP21 3AXD10000287428...
Page 187: ...Dimension drawings 187 Frame R9 IP55 3AXD10000334310...
Page 188: ...188 Dimension drawings...
Page 196: ...196 Resistor braking...