136 Technical data
Sizing
Drive sizing is based on the rated motor current and power. To achieve the rated
motor power given in the table, the rated current of the drive must be higher than or
equal to the rated motor current. Also the rated power of the drive must be higher
than or equal to compared to the rated motor power. The power ratings are the same
regardless of the supply voltage within one voltage range.
Note:
For frames R0…R3 the ratings apply at ambient temperature of 50 °C (122 °F)
for
I
N
. For frames R4…R9 in IP21, the ratings apply at ambient temperature of 40 °C
(104 °F) for
I
N
. Above theses temperatures derating is required.
The DriveSize dimensioning tool available from the manufacturer is recommended for
selecting the drive, motor and gear combination.
Derating
The load capacity (
I
N
,
I
Ld
,
I
Hd
; note that
I
max
is not derated) decreases for certain
situations, as defined below. In such situations, where full motor power is required,
oversize the drive so that the derated value provides sufficient capacity.
Note:
If several situations are present at a time, the effect of derating for each
situation is cumulative.
Example:
If your application requires continuous 12.0 A of motor current (
I
N
) at 8 kHz switching frequency,
the supply voltage is 400 V and the drive is situated at 1500 m, calculate the appropriate drive
size requirement as follows:
(page
The minimum size required is
I
N
= 12.0 A / 0.66 = 18.18 A,
where 0.66 is the derating for 8 kHz switching frequency (frames R0…R3).
(page
The derating factor for 1500 m is 1 - 1/10 000 m · (1500 - 1000) m = 0.95.
The minimum size required becomes then
I
N
= 18.18 A / 0.95 = 19.14 A.
Referring to
I
N
in the ratings tables (starting from page
), drive type ACS580-01-025A-4
exceeds the
I
N
requirement of 19.24 A.
I
Hd
Maximum current with 150% overload, allowed for one minute every ten minutes
1)
Maximum current with 130% overload, allowed for one minute every ten
minutes
2)
Maximum current with 125% overload, allowed for one minute every ten
minutes
P
Hd
Typical motor power in heavy-duty use (150% overload)
Summary of Contents for ACS580-01 drives
Page 1: ...ABB general purpose drives Hardware manual ACS580 01 drives 0 75 to 250 kW...
Page 4: ......
Page 11: ...Table of contents 11 Document library on the Internet 225...
Page 12: ...12 Table of contents...
Page 72: ...72 Planning the electrical installation...
Page 79: ...Electrical installation 79 R6 R9 3 3 4...
Page 132: ...132 Maintenance and hardware diagnostics...
Page 168: ...168 Dimension drawings Frame R0 IP21 3AXD10000257110...
Page 169: ...Dimension drawings 169 Frame R0 IP55 3AXD10000341562...
Page 170: ...170 Dimension drawings Frame R1 IP21 3AXD10000257188...
Page 171: ...Dimension drawings 171 Frame R1 IP55 3AXD10000336766...
Page 172: ...172 Dimension drawings Frame R2 IP21 3AXD10000257203...
Page 173: ...Dimension drawings 173 Frame R2 IP55 3AXD10000341578...
Page 174: ...174 Dimension drawings Frame R3 IP21 3AXD10000257219...
Page 175: ...Dimension drawings 175 Frame R3 IP55 3AXD10000335424...
Page 176: ...176 Dimension drawings Frame R4 IP21 3AXD10000332430...
Page 177: ...Dimension drawings 177 Frame R4 IP55 3AXD10000427933...
Page 178: ...178 Dimension drawings Frame R5 IP21 3AXD10000412280...
Page 179: ...Dimension drawings 179 Frame R5 IP55 3AXD10000415964...
Page 180: ...180 Dimension drawings Frame R6 IP21 3AXD10000258705...
Page 181: ...Dimension drawings 181 Frame R6 IP55 3AXD10000330667...
Page 182: ...182 Dimension drawings Frame R7 IP21 3AXD10000258995...
Page 183: ...Dimension drawings 183 Frame R7 IP55 3AXD10000330932...
Page 184: ...184 Dimension drawings Frame R8 IP21 3AXD10000287670...
Page 185: ...Dimension drawings 185 Frame R8 IP55 3AXD10000332446...
Page 186: ...186 Dimension drawings Frame R9 IP21 3AXD10000287428...
Page 187: ...Dimension drawings 187 Frame R9 IP55 3AXD10000334310...
Page 188: ...188 Dimension drawings...
Page 196: ...196 Resistor braking...