Page 48 May 2014 – TD 293 OPERATING MANUAL – SmartGuard 5100/5120/5300/5320
6.4.2
Completion of Digital sensor configuration
•
Perform sensor
User maintenance
settings:
Refer chapter 4.3 for a short description. User Maintenance
holds settings needed to operate the sensor in accordance with the way the user has chosen to apply the
actual sensor: open
Device Configuration
tab, check
Include User Maintenance
and press
Edit..
in the
User Maintenance heading. Refer Table 6-3, Table 6-4, and Table 6-5 for a description of settings.
•
Perform sensor
System Configuration
to enable sensor output parameters:
Refer chapter 4.2.3 for a short
description: open
Device Configuration
tab, and press
Edit..
in the System Configuration heading.
•
Add the sensor to the correct recording group, refer chapter 4.1.1.
Table 6-3 User Maintenance settings for Digital sensors of type Rain Fall.
Property
Comment
Mandatory:
Node description
Type a description. Default is product name and serial number
Filter
Minimum Pulse Spacing (ms)
Set appropriate value in accordance with manufacturer’s specification
in order to do ripple filtering on the signal
Calculations:
Unit
Set the Unit for the scaled/linearized value, e.g. mm
Range Min
Set the Range Min for the scaled/linearized value
Range Max
Set the Range Max for the scaled/linearized value
Unit/Pulse
Type
the scaling Unit/Pulse
according to the manufacturer’s
calibration, e.g. 0.2 mm/pulse
Table 6-4 User Maintenance settings for Digital sensors of type Frequency.
Property
Comment
Mandatory:
Node description
Type a description. Default is product name and serial number
Filter
Minimum Pulse Spacing (ms)
Set appropriate value in accordance with manufacturer’s specification
in order to do ripple filtering on the signal
Calculations:
Unit
Set the Unit for the scaled/linearized value, e.g. m/s
Range Min
Set the Range Min for the scaled/linearized value
Range Max
Set the Range Max for the scaled/linearized value
Coefficients
Type
polynomial coefficients for Set 1
.
Refer explanation in the
beginning of the chapter
Table 6-5 User Maintenance settings for Digital sensors of type Digital Logic.
Property
Comment
Mandatory:
Node description
Type a description. Default is product name and serial number