IM 05P02C41-01EN
10.8 Canceling Offset of PV and SP (Manual Reset)
Description
Manual reset can be used when the integral action is disabled.
When the integral action is disabled, there will be an offset of PV and SP. Manual reset
cancels this offset.
The manual reset value equals the output value when PV = SP is true.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
MR
Manual reset
EASY
-5.0 to 105.0%
PID
Note1: The PID number (1 to 8, or R) is displayed on Group display while each parameter is
displayed.
Note2: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.