8-57
IM 05P02C41-01EN
Control Functions
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
ZON
Zone PID
selection
STD
0: Segment PID selection
1: Zone PID selection (selection
by PV)
2: Zone PID selection (selection
by target SP)
4: Zone PID selection (selection
by SP)
5: Local PID selection
CTL
RP1 to RP7
Reference point 1
to 7
STD
0.0 to 100.0% of PV input range
(EU)
(RP1 ≤ RP2 ≤ RP3 ≤ RP4 ≤ RP5
≤ RP6 ≤ RP7)
ZONE
PID
PID number
(display only)
EASY
1 to 8, R: PID group for reference
deviation
MODE
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
Note2: A currently-used PID number is displayed for the parameter PID.
8
8.4 Switching PID
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...