11
All Rights Reserved. Copyright © 2010, Yokogawa Electric Corporation
GS 05P02C41-01EN Mar.14,2016-00
n
Terminal Arrangement
E4-terminal area
E3-terminal area
E2-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
408
409
410
411
412
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
209
210
211
212
101
-112
501
-512
401
-412
301
-312
201
-212
ALM
(Equipped
as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
PV event-2 output
PV event-3 output
PV event-1 output
Common
Common
Common
UP
104
105
106
107
108
109
PV
PV input
TC input
RTD input
Voltage (mV, V) input
A
+
-
+
-
Current (mA) input
+
-
B
b
(Equipped
as standard)
202
203
201
202
203
202
203
203
204
Factory default: PV input
type is undefined.
OUT
(Suffix code:
Type1=-0 or -2)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
In Heating/cooling control,
relay contact output is
heating-side output.
Factory default: Control
output is relay.
OUT
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12 V)
+
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Control output
(Suffix code: Type1=-0, -1 or -2)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
207
208
207
- 208
207
208
Can be used for retransmission output or 15 V DC loop power supply when
current/voltage pulse output is not used for control output.
Current output range can be changed.
In Position proportional type, can be used for retransmission output or 15 V
DC loop power supply.
OUT2
OUT2
(Suffix code: Type 1=-2)
Current/voltage pulse output
0-20 mA DC,
4-20 mA DC,
Voltage pulse (12V)
+
-
Retransmission output
+
-
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC,
4-20 mA DC
Cooling-side control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A
30 V DC, 3 A (resistance load)
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
511
512
507
508
509
511
512
511
512
Factory default: Cooling-side control output is
relay.
Can be used for retransmission output or 15 V
DC loop power supply when current/voltage
pulse output is not used for control output.
Current output range can be changed.
RET
Retransmission output
4-20 mA DC or
0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC
(Max. 21 mA DC)
+
-
+
-
Default: 4-20 mA DC
Default: PV
retransmission
Load resistance 600
Ω
or less
Retransmission output
(Equipped as standard)
205
206
205
206
Can be used for 15 V DC loop
power supply when not used for
retransmission output.
VALV
(Suffix code: Type1=-1)
Position proportional control output
Resistance: 100
Ω
to 2.5 k
Ω
Feedback input
100%
0%
Relay contact output
HIGH
(direct)
LOW
(reverse)
COM
Contact rating: 250 V AC, 3A
30 V DC, 3 A
(resistance load)
507
508
509
510
511
512
-
Feedback input
Current (mA)
input
When feedback input is current
510
511
512
+
HBA
(Option code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
510
511
512
HAL1
HAL2
COM
UP
507
508
509
112
(24 V AC/DC power supply:
Option code /DC)
Power supply
100-240 V AC power supply
N
L
Allowable range:
100-240 V AC (+10%/-15%)
(free voltage)
50/60 Hz shared
110
111
24 V AC/DC power supply
-
+
110
111
112
112
N
L
DI
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI3
DI2
DI1
COM
Common
DI3
DI2
DI1
COM
+5V
+5V
+5V
No-voltage
contact
Transistor contact
UP
UP
209
210
211
212
209
210
211
212
Functions can be changed.
Start of program operation when
DI1 switches from OFF to ON.
Stop of program operation when
DI2 switches from OFF to ON.
Start of local-mode operation when
DI3 switches from OFF to ON.
E1-Terminal Area
301-306
E2-Terminal Area
307-312
(Suffix code: Type 2=2)
Contact input
External contact input
DI11
DI12
DI13
DI14
DI15
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI13
+5V
DI14
+5V
DI15
+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UP
UP
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the
terminals with no function.
DI
Contact output
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
DO13
DO14
DO15
COM
Common
UP
(Suffix code: Type 2=3)
PV event-4 output
PV event-5 output
PV event-6 output
PV event-7 output
PV event-8 output
301
302
303
304
305
306
Function can be assigned to the
terminal with no function.
DO
(Suffix code: Type 2=1 or 4
and with option code /DR)
Universal input (Remote input)
TC input
RTD input
Voltage (mV, V) input
+
-
+
-
Current (mA) input
+
-
4-wire
302
303
302
303
303
304
RSP
a
B
b
A 301
302
303
305
Contact output
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO22
DO21
DO23
DO24
DO25
COM
Common
UP
(
Equipped as standard, however
suffix code: Type 2= except 4)
307
308
309
310
311
312
Function can be changed.
DO
Time event-5 output
Time event-4 output
Time event-3 output
Time event-2 output
Time event-1 output
(Suffix code: Type 2=4)
Aux. analog input
Default: 1-5 V DC
+
-
Aux. analog input / Contact input
External contact input
DI26
COM
Common
DI26
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
UP
UP
309
310
309
310
311
312
Function can be assigned
to the terminals with no
function.
AIN2
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
(Suffix code: Type 2=1 or 4
and without option code /DR)
Remote input
Default: 1-5 V DC
+
-
Remote input / Contact input
External contact input
DI16
COM
Common
DI16
COM
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
UP
UP
303
304
303
304
305
306
RSP
Specify within a
range of 1-5 V DC,
0-2 V DC,0-10 V DC
Start of remote-mode
operation when DI16
switches from OFF to ON.
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...