6-28
IM 05P02C41-01EN
Tuning Point and Storage Location of Tuning Results
The tuning point when performing auto-tuning is the target setpoint that is currently used
for control computation.
PID constants after the tuning are stored in the PID group that is specified when
performing auto-tuning.
Operation
mode
AT setpoint
Tuning point
Storage location
Program /
Local
1 to 8, R
Setpoint that is currently
used
P, I, and D of the PID group specified in
AT.
In Heating/cooling control: P, I, D, Pc, Ic,
and Dc
Remote
1 to 8, R
Remote setpoint
P, I, and D of the PID group specified in
AT.
In Heating/cooling control: P, I, D, Pc, Ic,
and Dc
When the setpoint of AT is “R,” the AT result is stored in the PID group for reference
deviation.
When performing auto-tuning in AT setpoint "R", set the parameter ZON to other than 0,
and set the parameter RDV to other than 0.
Auto-tuning cannot be performed when the control type (CNT) is as follows.
• ON/OFF control (1 point of hysteresis)
• ON/OFF control (2 points of hysteresis)
In addition, auto-tuning cannot be performed in the following cases (no error indication).
• Input error occurs. (Input burnout, ADC error, etc.)
• The operation mode is RESET.
• The operation mode is MAN.
• Output limiter setpoint at auto-tuning: AT.OL≥AT.OH
Start and Stop of Auto-tuning
Start and stop of auto-tuning can be set by parameter setting, communication, or contact
input.
Auto-tuning is stopped in the following cases.
• Switch to MAN
• Switch to RESET
• The parameter AT is set to OFF.
• Power failure
• Auto-tuning is not finished even after the time-out detection time is elapsed.
The time-out detection time is about 24 hours.
When the auto-tuning error occurs, the error code is shown in the Operation Display.
Press any key to erase it.
► Auto-tuning time output limiter: 8.9 Adjusting Auto-tuning Operation
6.2 Performing and Canceling Auto-tuning
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...