4-5
IM 05P02C41-01EN
Basic Operation
4
4.2 How to Set Parameters
The following operating procedure describes an example of setting alarm setpoint (A1).
Operation
1.
Hold down the
PARAMETER
key for 3 seconds in the Operation Display to call up
the [
MODE
] Menu Display.
2.
Press the
Right arrow
key to display the [
AL
] Menu Display.
3.
Press the
SET/ENTER
key to display the [
A1
] Parameter Setting Display.
4.
Press the
SET/ENTER
key to blink the setpoint.