8-19
IM 05P02C41-01EN
Control Functions
8
n
Cascade Position Proportional Control Function Block Diagram
Communication
COM
Aux. input
*1
SP limiter
Loop-1 PV input
Equipped as standard
(for Standard model)
Suffix code: Type 2 = 1 or 4 is necessary.
Loop-2 PV input
DI2
DI3
DI1
DI16
PV
RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
Ratio bias computation
Contact inputs
A.BS
A.FL
BS
FL
PMD
An, Bn
10-seg. linearizer approx./bias
PMD
An, Bn
10-seg. linearizer approx./bias
PV input bias
PV input filter
BS
FL
PMD
An, Bn
CNT
ALG
RMS
SPH, SPL
SPH, SPL
RFL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
A.BS
A.FL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
AIN2
PMD
An, Bn
A.BS
A.FL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
Tracking signal (Tracking when not in Cascade)
LSP
LSP
CAS
CAS
Switch to AUTO when
Loop-1 PV input burnout
or A/D error occurs.
Loop-2 local target setpoint
OH, OL
SP limiter
RUN
RESET
Remote input filter
Output limiter
Loop-1 control computation
Manual operation
Input error preset output
Preset output
When Loop-2 sensor burnout occurs
Normal
MAN
RUN
RESET
EPO
OH, OL
PO
CAS, AUTO
Output limiter
Signal comparison
Feedback input
Direct/reverse signal
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standard
Equipped as standard
Current
Current
OUT
RET
PMD
OU.H
OU.L
HYS
DB
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H
RET.L
PMD
An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
Valve position sliding
resistor or current
In Estimating-type position proportional control, the limiter function
does not work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
H relay
( key)
L relay
( key)
In Manual operation, the relay turns on while the or key is pressed.
Output limiter does not work.
(for Standard model)
DI16 is equipped when
suffix code: Type 2 = 1 or 4.
* The LP2 lamp is lit while the Loop-2 parameter is displayed.
Loop-2 control computation
Terminal
Parameter
Function
Analog signal
Contact signal
Front panel key
Legend
PV display
SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
PV display
SP display
(for Standard model)
Remote input can be used when
suffix code: Type 2 = 4.
Aux. analog (remote) input
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
Position Proportional Computation Output cannot be calculated by ladder program.
*
*
An external analog signal can
be used for Loop-2 SP. Use
the ladder program of LL50A
Parameter Setting Software
to build the function.
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
For the model with optional suffix code /DR:
Remote input with direct input
(E1-terminal area) can be used
when suffix code: Type 2 = 1 or 4,
and with optional suffix code /DR.
However, DI16 is to be deleted.
Program pattern selection
DI41 to DI45 are equipped when suffix
code: Type 2 = 0, 1 or 3.
The function is assigned to each DIs at
factory default.
Program pattern
Local target setpoint
Reset
TSP
S.PID
PTNO.
TIME
RAMP
L.PID
LSP
REM
LOC
RUN
RST
LSP/CAS
LSP
L.PID
RST
REM
LOC
RUN
LSP/CAS
RESET/RUN switch
RESET/RUN switch
LOCAL (ON) / CASCADE (OFF) switch
Start of program operation
when DI changes from OFF to ON.
Stop of program operation
when DI changes from OFF to ON.
Start of local-mode operation
when DI changes from OFF to ON.
Switch between the ON and OFF states of
each contact inputs to select from
program pattern numbers.
(Select a number during a RESET state.)
RST
REM
A/M
LOC
RUN
AL3
AL2
AL1
PV event 1
PV event 2
PV event 3
Time event 1
Time event 2
Time event 3
Time event 4
DO23
DO22
DO21
DO24
Time event 5
DO25
PV event, Time event, Alarm
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
RT
RBS
Preset output
PO
DO31 to DO35 are assinged Time event 6 to 10.
(for Detailed model)
Optional suffix code /R1 is necessary.
(for Detailed model)
DI16 is equipped when
optional suffix code /R1.
(for Detailed model)
Remote input can be used when
optional suffix code /A2.
For the model with optional suffix code /U1:
Remote input with direct input
(E1-terminal area) can be used
when optional suffix code /U1.
However, DI16 is to be deleted.
LPS
24 V loop
power supply
For optional suffix code /L4 or /LC4
Program pattern selection
DI41 to DI45 are equipped when optional
suffix code /X4.
The function is assigned to each DIs at
factory default.
** Loop-2 parameters.
**
**
**
**
**
**
**
SSP
8.1
Setting
Control
Mode
(CTLM)
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...