17-13
IM 05P02C41-01EN
Installation and W
iring
17
17.4.6 Contact Input Wiring
CAUTION
1) Use a no-voltage contact (relay contact etc.) for external contacts.
2) Use a no-voltage contact which has ample switching capacity for the terminal's
OFF voltage (approx. 5V) and ON current (approx 1mA).
3) When using a transistor contact, the voltage at both terminals must be 2 V or
less when the contact is ON and the leakage current must be 100 µA or less
when it is OFF.
4) If there is a risk of external lightning surges, use a lightning arrester etc.
Contact Input Equipped as Standard
No-voltage contact
Transistor contact
DI3
DI2
DI1
COM
209
210
211
212
DI
Contact rating: 12 V DC, 10 mA or more
DI3
DI2
DI1
COM
209
210
211
212
DI
+
+
+
–
+5 V
+5 V
+5 V
Contact rating: 12 V DC, 10 mA or more
Suffix code (for Standard model): Type 2≠2 or 4
Optional suffix code (for Detailed model):/X4
No-voltage contact
Transistor contact
DI41
DI42
DI43
DI44
DI45
COM
Contact rating: 12 V DC, 10 mA or more
501
502
503
504
505
506
DI
DI41
DI42
COM
DI43
DI44
DI45
501
502
503
504
505
506
DI
+5 V
+5 V
+5 V
+5 V
+5 V
Contact rating: 12 V DC, 10 mA or more
+
+
+
+
+
–
17.4 Wiring
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...