11-4
IM 05P02C41-01EN
Deviation within High and Low Limits Alarm, Deviation(%) within High and
Low Limits Alarm
PV
Alarm hysteresis
Alarm hysteresis
Deviation within high
and low limits alarm setpoint
Time
ON
ON
OFF
OFF
ON
Deviation within
high and low limits
alarm output
Target setpoint
(SP)
Contact type in the figure above: Energized when an event occurs (factory default).
Set the alarm setpoint and hysteresis for a deviation(%) within high and low limits as
percentages of the setpoint.
Target SP High Limit Alarm and Target SP Low Limit Alarm
ON
ON
Taraget SP
OFF
OFF
Contact type in the figure above: Energized when an event occurs (factory default).
Time
Target SP high limit
alarm setpoint
Target SP low limit
alarm setpoint
Target SP high limit
alarm output
Target SP low limit
alarm output
Alarm hysteresis
SP changing
SP changing
SP changing
SP changing
SP in ramp rate setting
Alarm hysteresis
11.1 Setting Alarm Type
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...