8-41
IM 05P02C41-01EN
Control Functions
n
Position Proportional Loop Control with PV Auto-selector (4 inputs) Function Block Diagram
COM
SP limiter
DI26 DI46
PV
AIN2
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
10-seg. linearizer approx./bias
PV input bias
PV input filter
Ratio bias computation
PV auto-selector (Max., Min., Ave., Diff.)
A.BS
A.FL
BS
FL
PMD
An, Bn
10-seg. linearizer approx./bias
PMD
An, Bn
10-seg. linearizer approx./bias
PMD
An, Bn
10-seg. linearizer approx./bias
PMD
An, Bn
10-seg. linearizer approx./bias
PMD
An, Bn
PV.AS
P.UNI
P.DP P.RH, P.RL
CNT
ALG
SPH, SPL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
A.BS
A.FL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
RSP
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
A.BS
A.FL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
AIN4
Input type
Input unit
Input range/scale
Analog input bias
Square root extraction
Analog input filter
A.BS
A.FL
A.SR
A.LC
UNIT
IN
RH, RL
SDP
SH, SL
DI16
DI2
DI3
DI1
Control computation
Manual operation
Input error preset output
Preset output
AUTO
Normal
MAN
RUN
RESET
Output limiter
EPO
OH, OL
PO
Signal comparison
Feedback input
Direct/reverse signal
Valve position sliding
resistor or current
Motor-operated valve
Relay output
VALV
FBIN
M
Equipped as standard
Equipped as standard
Current
Current
OUT
RET
PMD
OU.H
OU.L
HYS
DB
An, Bn
Split computation
10-seg. linearizer approx./bias
RET.H RET.L
PMD
An, Bn
Split computation
10-seg. linearizer approx./bias
OUT retransmission output
O1RS
RET retransmission output
RTS
PV input 1
PV input 2
PV input 3
PV input 4
Contact inputs
(for Standard model) Suffix code: Type 2 = 1 or 4 is necessary.
(for Standard model)
When suffix code: Type 2 = 4
(for Standard model)
When suffix code: Type 2 = 4
Aux. analog (remote) input (E1-terminal area)
Aux. analog input (E2-terminal area)
Aux. analog input (E4-terminal area)
Equipped as standard
Necessary for Loop control with PV auto-selector for 3 inputs or 4 inputs
For the model with optional suffix code /DR:
Refer to the function block diagram of
Loop control with PV auto-selector (2 inputs).
When sensor
burnout occurs
In Estimating-type position proportional control, the limiter function does not
work on output operation.
The reverse-signal relay turns on when being limited by low limit.
The direct-signal relay turns on when being limited by high limit.
Sensor burnout occurs when PV, RSP, AIN2, or AIN4 input burnout occurs.
However, burnout is not detected if input is not conncted.
Position Proportional Computation Output cannot be calculated by ladder program.
In Manual operation, the relay turns on while the
or key is pressed. Output limiter does not work.
H relay
( key)
L relay
( key)
Terminal
Parameter
Function
Analog signal
Contact signal
Front panel key
Legend
PV display
SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
RMS
*1: RS-485, Ethernet, PROFIBUS-DP,
DeviceNet, CC-Link
(for Standard model)
DI16 is equipped when
suffix code: Type 2 = 1 or 4.
DI26 and DI46 are equipped when
suffix code: Type 2 = 4.
Program pattern
Local target setpoint
Reset
TSP
S.PID
PTNO.
TIME
RAMP
L.PID
LSP
REM
LOC
RUN
RST
Program pattern selection
Switch between the ON and OFF
states of each contact inputs to
select from program pattern
numbers.
(Select a number during a RESET
state.)
DI41 to DI45 are equipped when suffix code:
Type 2 = 0, 1 or 3.
The function is assigned to each DIs at
factory default.
RT
RBS
RESET/RUN switch
RST
REM
A/M
LOC
RUN
AL3
AL2
AL1
PV event 1
PV event 2
PV event 3
PV event
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
No function is
assigned to
DI16, DI26,
and DI46.
Start of program operation
when DI changes from OFF to ON.
Stop of program operation
when DI changes from OFF to ON.
Start of local-mode operation
when DI changes from OFF to ON.
LPS
24 V loop
power supply
For optional suffix code /L4 or /LC4
Program pattern selection
DI41 to DI45 are equipped when optional
suffix code /X4.
The function is assigned to each DIs at
factory default.
(for Detailed model) Optional suffix code /R1 is necessary.
(for Detailed model)
When optional suffix code /A2
(for Detailed model)
When optional suffix code /A4
For the model with optional suffix code /U1:
Refer to the function block diagram of
Loop control with PV auto-selector (2 inputs).
(for Detailed model)
DI16 is equipped when
optional suffix code /R1.
DI26 and DI46 are equipped when
optional suffix code /A2 and /A4.
SSP
8
8.1
Setting
Control
Mode
(CTLM)
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...