8-67
IM 05P02C41-01EN
Control Functions
8.8 Performing Non-linear PID Control
Description
If a deviation (E) is smaller than the non-linear control gap width (GW), it is computed as
a proportional added the non-lenear control gain (GG).
Proportional Band (CPB) = Proportional Band (P) / GG
* | E | ≤ GW / 2
However, CPB is limited by 0.1 to 999.9%.
0%
100%
SP=EU(50%)
EU(100%)
EU(0%)
PV
PV
OUT
OUT
GW
Control output will change smoothly (i.e., without any bumps) when CPB switches.
Note
In heating/cooling control, do not use non-linear PID control.
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
GW
Non-linear control gap width
PRO
OFF, 0.0%+1digit to 50.0%
of PV input range span
(EUS)
TUNE
GG
Non-linear control gain
PRO
0.001 to 1.000
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
8
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...