18-12
IM 05P02C41-01EN
Local Setting Menu (Menu: LOC)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
LSP
Local target
setpoint
EASY
0.0 to 100.0% of PV input range (EU) (Setting
range: P.RL to P.RH)
P.RL
L.PID
PID number
selection
for local-
mode
operation
EASY
Set a PID group number to use.
1 to 8
* Available only for the L.PID when ZON = 0 or 5.
* If set to “Local PID selection,” local PID is
selected irrespective of the operation modes.
1
L.TY1 to
L.TY8
Local
event-1 to -8
type
STD
OFF: Disable
(Energized)
1: PV high limit,
2: PV low limit,
3: SP high limit,
4: SP low limit,
5: Deviation high limit,
6: Deviation low limit,
7: Deviation high and low limits,
8: Deviation within high and low limits,
9: Target SP high limit,
10: Target SP low limit,
11: Target SP deviation high limit,
12: Target SP deviation low limit,
13: Target SP deviation high and low limits,
14: Target SP deviation within high and low limits,
15: OUT high limit,
16: OUT low limit,
17: Cooling-side OUT high limit,
18: Cooling-side OUT low limit
* Add 100 for "de-energized". For example,
when the PV high limit is de-energized, the
setting is 101.
OFF
L.EV1 to
L.EV8
Local
event-1 to -8
setpoint
STD
Set a display value of setpoint of PV alarm, SP
alarm, deviation alarm, or output alarm.
-19999 to 30000 (Set a value within the input range.)
Decimal point position depends on the input type
0
When the program pattern-2 retransmission is selected (PT2.G=ON), the second loop is also
displayed for the parameter LSP. (LP2 lamp is lit.)
Program Editing Menu (Menu: EDIT)
Parameter
symbol
Name
Display
level
Setting range
Initial value
ALL.S
Number of remaining
unused segments
PRO
0 to 300 (600 when the option “/
AP” is specified)
(Display only)
300
PTN.S
Pattern number
designation for
comfirming number
of segments
PRO
Specify the numbers of program
pattern to display in parameter
USE.S.
1 to 30 (99 when the option “/AP”
is specified)
0
USE.S
Number of segments
within a pattern
PRO
Can be displayed when the
parameter number specify in
parameter PTN.S. (Display only)
0: disable
1 to 99
-
CPY.S
Source-of-copying
pattern number
designation
PRO
Specify the number of the source-
of-copying program pattern. (1 to
30 (99 when the option “/AP” is
specified))
0
CPY.D
Target-of-copying
pattern number
designation
PRO
Specify the target-of-copying
program pattern. (1 to 30 (99 when
the option “/AP” is specified))
0
CLR.P
Program pattern
clearance
PRO
Specify the number of the
program pattern to be cleared. (1
to 30 (99 when the option “/AP” is
specified))
0
18.2 List of Parameters
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...