5-3
IM 05P02C41-01EN
Quick Setting Function
5
Setting Example
Set the following parameters to set to PID control, thermocouple Type K (range: 0.0 to
500.0ºC), and current control output. No need to change the parameters other than the
following parameters.
Set QSM = YES to enter the quick setting mode.
(1) Set CNT = PID.
(2) Set IN = K1.
(3) Set UNIT = C (initial value).
(4) Set RH = 500.0.
(5) Set RL = 0.0.
(6) Set OT = 00.02
Set EXIT = YES to quit the quick setting mode.
The Operation Display is shown.
Setting Details
Control Type
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
CNT
Control type
EASY
PID: PID control
ONOF: ON/OFF control (1 point of
hysteresis)
ONOF2: ON/OFF control (2 points
of hysteresis)
H/C: Heating/cooling control
CTL
Note1: In Cascade control, the LP2 lamp is lit while the Loop-2 parameter is displayed.
► Control type: 8.2 Setting Control Type (CNT)
5.1 Setting Using Quick Setting Function
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...