18-8
IM 05P02C41-01EN
18.2 List of Parameters
18.2.1 Operation Parameters
Operation Mode Menu (Menu:
MODE)
Parameter
symbol
Name
Display
level
Setting range
Initial
value
HOLD
Pause/cancel
release of program
operation
EASY
ON: Pause
OFF: Cancel release (Program
operation restart)
Display during program operation.
OFF
ADV
Advance of
segment
EASY
OFF: -
Display during program operation.
Set as “ADV = ON” to advance from
the current segment to the next
segment.
OFF
MODE
Operation mode
EASY
RESET: Stop of program operation
PROG: Start of program operation
LOCAL: Start of local-mode operation
REM: Start of remote-mode operation
RESET
A.M
AUTO/MAN switch
EASY
AUTO: Automatic mode
MAN: Manual mode
MAN
L.C
LOCAL(LSP)/CAS
switch
EASY
LSP: Local (LSP)
CAS: Cascade
CAS
PTNO.
Program pattern
number selection
EASY
0: Not select program pattern
1 to 30 (99 when the option “/AP” is
specified)
0
SST
Start-of-program
segment
number
EASY
1 to 99
The setting value returns to “1” when
the program operation (PROG)
changes into RESET, LOCAL, or REM.
1
P.FWD
Fast-forwarding of
program operation
EASY
1: Normal, 2: Twice, 5: Five times, 10:
Ten times, 20: Twenty times
* Use this function when checking
the program pattern setting. Only
Segment time and Time event can
be faster.
* The operation returns to the normal
speed after fast-forwarding.
1
AT
Auto-tuning switch
EASY
OFF: Disable
1 to 8: Perform auto-tuning. Tuning
result is stored in the specified
numbered PID.
R: Tuning result is stored in the PID for
reference deviation.
OFF
PID
PID number
EASY
The PID group number being selected
is displayed. (display only)
1 to 8, R: PID group for reference
deviation
1
In Cascade control, the following operation modes are also displayed for secondary loop. (the LP2
lamp is lit)
• Operation mode: A.M, AT, PID
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...