7-11
IM 05P02C41-01EN
Input (PV
, Remote, and
Auxiliary
Analog) Functions
Setting Details
Parameter
symbol
Name
Display level
Setting range
Menu symbol
PYS
10-segment
linearizer
selection
Group 1, 2: STD
Group 3, 4: PRO
OFF: Disable
PV: PV analog input
RSP: RSP analog input
AIN2: AIN2 analog input
AIN4: AIN4 analog input
PVIN: PV input
OUT: OUT analog output
OUT2: OUT2 analog output
RET: RET analog output
PYS1
PYS2
PYS3
PYS4
A1 to A11
10-segment
linearizer
input
Group 1, 2: STD
Group 3, 4: PRO
-66.7 to 105.0% of input range
(EU)
Output linearizer: -5.0 to 105.0%
B1 to B11
10-segment
linearizer
output
Group 1, 2: STD
Group 3, 4: PRO
10-segment linearizer bias: -66.7
to 105.0% of input range span
(EUS)
10-segment linearizer
approximation: -66.7 to 105.0%
of input range (EU)
Output linearizer: -5.0 to 105.0%
PMD
10-segment
linearizer
mode
Group 1, 2: STD
Group 3, 4: PRO
0: 10-segment linearizer bias
1: 10-segment linearizer
approximation
Note1: When each parameter is displayed, the group number (1 to 4) is displayed on Group display.
Parameters are set in the following order.
(1) PYS: Specifies where the 10-segment linearizer function is used.
Setpoints PV, RSP, AIN2, and AIN4 function before the input ladder calculation
section.
Setpoint PVIN functions after the input ladder calculation section.
► Where the 10-segment linearizer function is used; Function block diagrams in 8.1 Setting
Control Mode (CTLM)
(2) PMD: Specifies whether to use it as a 10-segment linearizer bias or a 10-segment
linearizer approximation.
(3) A1 to A11, B1 to B11: Sets the 10-segment linearizer input and 10-segment linearizer
output.
For the input range and input range span, the range varies depending on where the
10-segment linearizer is used.
PV input and PV analog input: PV input range or PV input range span
RSP analog input: RSP remote input range or RSP remote input range span
AIN2 auxiliary analog input: AIN2 auxiliary analog input range or AIN2 auxiliary
analog input range span
AIN4 auxiliary analog input: AIN4 auxiliary analog input range or AIN4 auxiliary
analog input range span
Note
• Set the 10-segment linearizer so that it increases monotonically.
• If the same setpoint is set for the two or more parameters of 10-segment linearizer selection
(PYS), a smaller group number is used.
7
7.1 Setting Functions of PV Input, Remote Input, and Auxiliary Analog Input
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...