7-12
IM 05P02C41-01EN
Initial value of eatch control mode
Control mode
Group-1 PYS Goup-2 PYS Group-3 and -4 PYS
Single-loop control
PV
OFF
OFF
Cascade primary-loop control
PV
OFF
OFF
Cascade control
PV
RSP
OFF
Loop control with PV switching
PV
OFF
OFF
Loop control with PV auto-selector
PVIN
OFF
OFF
7.1.5 Setting Ratio bias/filter
Description
Ratio bias computing performs ratio computation and bias addition for remote setpoints.
SP = Remote input x Remote input ratio (RT) + Remote input bias (RBS)
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
RT
Remote input ratio
STD
0.001 to 9.999
SPS
RBS
Remote input bias
STD
100.0 to 100.0% of PV
input range span (EUS)
RFL
Remote input filter
STD
OFF, 1 to 120 s
Note 1: In Cascade control, PV input terminal is for Loop 1 and RSP remote input terminal is for
Loop 2. The LP2 lamp is lit while the Loop-2 parameter is displayed.
7.1 Setting Functions of PV Input, Remote Input, and Auxiliary Analog Input
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...