9-16
IM 05P02C41-01EN
(2) When LSP and SSP are different
Seg.1
Seg.2
Seg.3
TSP
SSP
TSP
TSP
Local target
setpoint (LSP) in
Local operation
Seg.: Segment
Program pattern
for control
Program operation start (LOC → PRG)
Time
Setpoint
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
SSP
Starting target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU)
(Setting range: P.RL to P.RH)
PROG
STC
Start code
EASY
SSP: Program operation begins
with the starting target setpoint.
RAMP: Ramp-prioritized PV start
TIME: Time-prioritized PV start
LSP: Local-mode start
RSP: Remote-mode start
LSP
Local target
setpoint
EASY
0.0 to 100.0% of PV input range
(EU)
(Setting range: P.RL to P.RH)
LOC
Note 1: When the program pattern-2 retransmission is selected (PT2.G=ON), the second loop is
also displayed for the parameter SSP. (LP2 lamp is lit.)
9.3 Setting the Program Starting Conditions (STC)
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...