7.4 Using Larger, Smaller, Average, or Difference
of Two to Four Inputs as PV
Description
Loop control with PV auto-selector function automatically selects or calculates the larger,
smaller, average, or difference of multiple (two to four) inputs and uses the result as PV.
The larger, smaller, and average are automatically computed based on the specified
number of inputs.
For the input difference, the difference between input 1 and input 2 is computed.
Input 1: PV terminal input
Input 2: RSP terminal input
Input 3: AIN2 auxiliary analog input
Input 4: AIN4 auxiliary analog input
► Function block diagram for Loop control with PV auto-selector; 8.1.5 Loop Control with PV Auto-
selector, Heating/cooling Loop Control with PV Auto-selector, and Position Proportional Loop
Control with PV Auto-selector
Setting Details
Parameter
symbol
Name
Display
level
Setting range
Menu symbol
PV.AS
Input computation
selection
STD
0: Max. value
1: Min. value
2: Ave. value
3: Input 1 - Input 2
4: Input 2 - Input 1
MPV
PV.NU
Number of inputs
STD
2: Use Input 1 and Input 2
3: Use Input 1, Input 2, and
Input 3
4: Use 4 inputs
7
Содержание UTAdvanced UP55A
Страница 3: ......
Страница 21: ...Blank Page ...
Страница 37: ...Blank Page ...
Страница 47: ...Blank Page ...
Страница 125: ...Blank Page ...
Страница 147: ...Blank Page ...
Страница 155: ...8 8 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 159: ...8 12 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 167: ...8 20 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 175: ...8 28 IM 05P02C41 01EN Intentionally blank 8 1 Setting Control Mode CTLM ...
Страница 221: ...Blank Page ...
Страница 275: ...Blank Page ...
Страница 351: ...Blank Page ...
Страница 381: ...Blank Page ...
Страница 403: ...Blank Page ...
Страница 491: ...Blank Page ...
Страница 505: ......
Страница 513: ...Blank Page ...
Страница 515: ...Blank Page ...