10.5 Blow back
This section explains the parameter settings for performing blow back.
10.5.1 Mode
There are three modes of blow back operation: no function, semi-automatic, and automatic.
Blow back is not performed when the mode is set to [No function]. In [Semi-auto] mode, blow back
can be started by key operation on the display or by a contact input signal, and then sequentially
performed at a preset blow back time and hold time. In [Auto] mode, blow back is automatically
performed at preset intervals. For [Semi-auto] or [Auto] modes, blow back is performed one channel
at a time until all channels have been covered. The following restrictions apply:
* When [No function] is selected: Blow back is not performed
* When [Semi-auto] is selected: Semi-automatic blow back can be performed.
(Blow back does not start at Automatic blow back start time.)
* When [Auto] is selected:
Blow back can be performed in either [Auto] or [Semi-auto] mode.
<Setting Procedure>
1) From the basic panel display, touch Setup key; on the [Execution/Setup] display which appears,
select [Maintenance].
2) On the [Maintenance] display, select [Blow back setup] and the Mode selection pulldown allows
you to select between [No function], [Semi-auto] and [Auto] (see Figure 10.23).
Enter
F10-23E.ai
Mode: Auto
Hold time: 1 0 min 0 0 s
Blow back time:
3 0 min 0 0 s
Blow back setup
No function
Semi-auto
Auto
Figure 10.23 Mode Selection