< 4. Piping >
4-7
IM 11M12D01-01E
4.1.7 Piping to Introduce Purge Gas When a Process Gas Alarm Occurs
When a process gas alarm (an input contact signal of unburnt gas detection) occurs, the averaging
converter will cut off the power supply to the heater of the detector, and at the same time it will send a
contact output to activate a solenoid valve for introducing a purge gas to the detector.
In addition to the system configuration shown in Figure 4.1, a purge gas cylinder and a pressure
reducing valve, and where necessary, a stop valve, a flowmeter, and a needle valve are required.
Also, a check valve should be installed on the calibration gas inlet of the detector. A typical piping
diagram for purging is shown in Figure 4.9.
It is recommended that each instrument be installed to allow for minimum piping between the ZA8F
Flow Setting Unit and the detector and between the solenoid valve for introducing the purge gas and
the detector.
Check valve
Check valve
To ZA8F
Calibration gas line
Reference gas line
To ZA8F
Averaging Converter (AV550G)
Heater
Signal
Contact output
Purge gas cylinder
Flowmeter
Pressure
reducing valve
Needle valve
Reference gas line
Calibration gas line
Solenoid valve
Detector
Power supply
Contact input
Contact output
Analog outputs:
(Averaged and
individual outputs)
Stop valve
F4-9E.ai
Figure 4.9 Typical Piping for Purging