< 5. Wiring >
5-12
IM 11M12D01-01E
5.2.10 Wiring for Contact Inputs
The averaging converter receives contact inputs to perform the specified functions.
Follow the instructions below to run the wiring for contact inputs.
Use 2-core or 3-core cable that withstand temperatures of at least 80°C for this wiring. The number of
cores is determined by the number of contacts to be used. There is no need to use shielded cables. If
a cable gland is not installed on the wiring hole of the averaging converter, use a wire with an outside
diameter of 17 mm or smaller. If installed, use a wire with an outside diameter of 6 to 12 mm. Like the
signal wiring to detectors, the shields should be connected to cable shield ground terminals on the
case of the averaging converter.
Contact inputs should be voltage free. The open/closed state of the contact is determined by the
resistance from the averaging converter side. Note that the resistance should include the wiring
resistance.
Closed contact: 200 Ω or less
Open contact: 100 kΩ or more
7
8
9
Averaging Converter
Control Card
Contact Input 1
Contact Input 2
F5-14E.ai
DI1
DI2
COM
Figure 5.14 Wiring for Contact Inputs