IM 1C21D1-01E
10-7
10. GENERAL SPECIFICATIONS
Item
Description
Code
Painting
Color change
Coating change
Lightning protector
Calibration units
Sealing treatment to
SUS630 nuts
Long vent
(Note 1)
P
h
X1
A
K1
D1
D3
D4
Y
U
(See Table for Span
and Range Limits)
Amplifier cover only
Epoxy resin-baked coating
Transmitter power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically
safe type, 9 to 32 V DC for Fieldbus communication type.)
Allowable current: Max. 6000 A (1
3
40
µ
s), Repeating 1000 A, 100 times
Degrease cleansing treatment
P calibration (psi unit)
bar calibration (bar unit)
M calibration (kgf/cm
2
unit)
Sealant (liquid silicone rubber) is coated on surfaces of SUS630 nuts used
for cover flange mounting.
Total vent plug Length: 112 mm (standard, 32 mm)
Gold-plate
A1
Gold-plated diaphragm
High Accuracy Type
HAC
High Accuracy (Applicable only for Model EJA310A)
K2
Degrease cleansing treatment and with fluorinated oil filled capsule.
Operating temperature –20 to 80
8
C
Oil-prohibited use
130 Pa abs {1 mmHg abs}
(Note 4)
S1
Minimum input pressure: 130 Pa abs{1 mmHg abs} at range calibrating testing
Mill Certificate
Cover flange
Cover flange, Process connector
Test Pressure: 50 kPa{0.5 kgf/cm
2
} Capsule L, M
Test Pressure: 3 MPa{30 kgf/cm
2
} Capsule A
Test Pressure: 14 MPa{140 kgf/cm
2
} Capsule B
Test Pressure: 32 MPa{320 kgf/cm
2
} Capsule C
Test Pressure: 50 MPa{500 kgf/cm
2
} Capsule D
(Note 5)
M01
M11
T04
T03
T02
T09
T08
Pressure test/
Leak test Certificate
Nitrogen(N
2
) Gas
(Note 7)
Retention time: 10 minutes
K5
Degrease cleansing treatment and dehydrating treatment
K6
Degrease cleansing treatment and dehydrating treatment with fluorinated oilfilled capsule.
Operating temperature –20 to 80
8
C
Oil-prohibited use
with dehydrating treatment
Stainless steel
amplifier housing
(Note 3)
Amplifier housing material; SCS14A stainless steel (equivalent to SUS316 cast stainless
steel or ASTM CF-8M)
E1
(Note 6)
T1010.EPS
Failure alam down-scale
(Note 2)
Fast response
F1
C1
Updete time: 0.125 sec or less, see GS for response time
Output status at CPU failure and hardware error.
When combining with Optional code F1, output signal is –2.5%, 3.6 mA DC or less.
Body option
Stainless steel tag plate
N1
N2
N3
N4
Without drain and vent plugs
N1 and Process connection on both sides of cover flange with blind kidney flanges
on back
N1, /N2, and Mill certificate for cover flange, diaphragm, capsule body, and blind
kidney flange
JIS SUS 304 stainless steel tag plate wired onto transmitter
Custom software configuration (Applicable only for Model EJA430A)
Configuration
R1
Note 1: Applicable only for vertical impulse piping types (Installation Code 2, 3, 6 or 7). Long vent
material is SUS316.
Note 2: The hardware error indicates faulty amplifier or capsule. Standarard output status (without /C1)
is up-scale of 110%, 21.6 mA DC or more.
Note 3: Applicable for Electrical Connection Code 2, 3, 4 and 7. Not applicable for Optional Code P
h
and X1.
Note 4: Applicable only for Capsule Code M and A and smaller value than 53.3 kPa {400 mmHg abs} of
higher range value (HRV).
If Optional Code S1 is not specified, minimum input pressure will be 2.7 kPa abs {20 mmHg
abs} for calibration testing.
For Capsule Code L, the Optional Code S1 is covered by standard feature. (Optional Code S1
is not required to Capsule Code L.)
Note 5: Applicable for Process Connections Code 0 and 5.
Note 6: Applicable for Process Connections Code 1, 2, 3 and 4.
Note 7: Pure nitrogen gas is used for Oil-prohibited use (Optional Code K1, K2, K5 and K6).