IM 1F6A0-01E
3-7
3. INSTALLATION
Table 3.3(a) Installation of Wafer Type Vortex Flowmeter
Size mm(inch)
Flange Rating
15 to 40
(1/2 to 1-1/2)
50(2)
80(3)
All ratings
JIS 10K, ANSI class 150
ANSI class 150
Horizontal Installation
When Installation Collar are required, the
installation vortex flowmeters applied to the
following line sizes and flange ratings.
The inside diameter of the gasket must
be larger than the pipe inner diameter
so that it will not disturb the flow in the
pipeline.
(1) Insert two each collars on
each of the lower two bolts.
(2) Place the flowmeter body
on the lower two bolts.
(3) Tighten the four bolts
(including upper two bolts)
and nuts uniformly.
(4) Check for leakage from
the flange connections.
(1) Insert four collar on each of the four bolts and check
that all four collars contact the outside diameter of
the flowmeter body.
(2) Tighten the four bolts uniformly. Check for leakage
from the flange connections.
Vertical Installation
When installing the Flowmeter vertically in the
open air, change the electrical connection port
direction to the ground. If the electrical
connection port is installed upwards, rain
water might leak in.
WARNING
Wafer type
Description
When Installation Collars are not required,the
installation vortex flowmeters applied to the
following line sizes and flanges.
Size mm(inch)
Flange Rating
50(2)
80(3)
100(4)
JIS 20K, 40K
ANSI class 300,600
JPI class 300,600
JIS 10K, 20K, 40K
ANSI class 300, 600
JPI class 300,600
JIS 10K, 20, 40K
ANSI class 150, 300, 600
JPI class 150,300,600
Horizontal Installation
Vertical Installation
(1) Insert two stud bolts in the bolt holes
on the flowmeter shoulder to align
the instrument body with the inner
diameter of the adjacent piping.
(2) Tighten all bolts uniformly and check
that there is no leakage between the
instrument and the flanges.
WARNING
T030602.EPS
Flange
Nut
Nut
Gasket
Collar
Electrical
connection
Flow Direction
Flow Direction
Gasket
Flange
Flow
Direction
Stud Bolt (4 pcs.)
Nut
Nut
Gasket
Bolt Hole
Gasket
Flange
Flange
Flow
Direction
Stud Bolt (8 pcs.)
Electrical Connection
Electrical Connection
Electrical