IM 1F6A0-01E
5-9
5. BASIC OPERATING PROCEDURES
5.5 Operation for the BT200
This section decribes the operation procedures using a brain
terminal (BT200). For details on the functions of the
YEWFLO, refer to “6.2 Parameter List”. And also, see the
“BT200 Instruction Manual” (IM 1C0A11-01E) for more
detailed Information.
5.5.1 Connection Method of the BT200
(1) Connecting the BT200 to a 4 to 20mA DC
Transfer Line
The communication signal of the YEWFLO is superim-
posed onto the 4 to 20mA DC analog signal to be
tranferred.
YEWFLO
SUPPLY
BT200
BT200
BT200
BT200
Inter mediate
terminals
4 to 20mA DC
Signal
transmission
line
Control room
Receiver
Resistance
250 to 600
Ω
Receiving
instrument
Terminal
Board
SUPPLY
F050404.EPS
Figure 5.4
Communicating for a 4 to 20mA DC Signal
Line
IMPORTANT
The communicable distance of the transmission line is
restricted depending on the wiring method. Refer to “4
: WIRING”.
IMPORTANT
After setting a parameter, keep the power on for at
least 30 seconds.
If the power of flowmeter is turned off, a parameter
setting is released.
(2) Connecting BT200 to Flow Converter
Removing a cover and indicator, the terminals for brain
communication are provided on the circuit board.
Connect BT200 to the terminal of HHT-COM on the
circuit board.
TP2
COM
HHT
P
F050405.EPS
Display
BT200
Indicator Mounting
Screw (2 PCS)
Circuit board
Figure 5.5
Connection of BT200 to Flow Converter