IM 1F6A0-01E
5-17
5. BASIC OPERATING PROCEDURES
5.6.6 Unique Functions of HART Commu-
nicator
Check on communication error
When each error, over run framing error, parity error or
buffer overflow error is detected, the data including the
informations of errors is returned, and the error message is
indicated on HHT.
Real time monitoring 4-20mA output
‘%’ output, actual flow rate and totalized value are men-
tioned as same as BRAIN communicator. And furthermore 4-
20mA output is monitored on real time.
Time recording
Online
⇒
1.Device setup
⇒
4.Detailed setup
⇒
4. Device info
⇒
5.Date
F050604_1.EPS
Day, month and year can be set in a number of 2 figures.
Multi drop communication
Field devices in multidrop mode refer to the connection of
several field devices on a communication single line. Up to
15 field devices can be connected when set in the multidrop
mode. To activate multidrop communication, the field device
address must be changed to a number from 1 to 15. This
change deactivates the 4 to 20mA output and turns it 4mA
output and turns it 4mA.
Online
⇒
1.Device setup
⇒
4.Detailed setup
⇒
4.Device info
⇒
6.Dev id
F050604_2.EPS
Continuously data returning (Burst mode)
YEWFLO continuously sends the data stored in it when the
burst mode it set “ON”. Either one of instantaneous flow
rate, output in % and current output can be selected and sent.
(Note: This mode is preserved after the converter has been
turned off.)
The interval of sending data in this mode is the same as the
common specification of HART communicator.
*Calling up “Burst option” display.
CAUTION
In case of using Burst mode, setting from AMP. unit is
not available
Online
⇒
1.Device setup
⇒
4.Detailed setup
⇒
3.Output setup
⇒
6.HART output
⇒
3.Burst mode
⇒
1.Burst option
F050604_3.EPS
Multi HHT communication
Corresponding to discriminating communication between two
HHTs.
Device ID setting
Device ID is set in an unsigned integer number of 3 bytes.