12 Fault Diagnosis and Possible Solutions
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
59
Minor Faults and Alarms
Table 25 Alarm Codes, Causes, and Possible Solutions
Prior to Installing the Option
Prior to installing the option, wire the drive, make the necessary connections to the drive terminals, and verify that the
drive functions normally. Refer to the
Table 26
for information on wiring and connecting the drive.
Table 26
below lists the number of option cards that can be connected to the drive and the drive connectors for
connecting those option cards.
Table 26 Option Card Installation
LED Operator Display
Minor Fault Name
CALL
Serial communication transmission error
Communication is not established.
Cause
Possible Solution
Minor Fault
(H2-
= 10)
Communication wiring is faulty, there is a short
circuit, or improper connection.
Check for wiring errors:
• Correct the wiring.
• Remove ground shorts and reconnect loose wires.
YES
Programming error on the master side.
Check communications at start-up and correct programming errors.
Communication circuitry is damaged.
• Perform a self-diagnostics check.
• Replace the drive if the fault continues to occur.
Digital Operator Display
Minor Fault Name
EEP
EEPROM Error
EEPROM checksum error
Cause
Possible Solution
Minor Fault
(H2-
= 10)
Communication wiring is faulty, there is a short
circuit, or something is not connected properly.
Check for wiring errors.
• Correct the wiring.
• Remove and ground shorts and reconnect loose wires.
YES
EEPROM checksum error
If these errors occur, the object dictionary will be reset to its default
values.
• After the object dictionary has been changed and object dictionary
contents are then changed, execute a Store Parameter command
(Index = 1010 (Hex)).
• If the object dictionary has not been changed, execute a Restore
Parameter command (Index = 1011 (Hex)).
Option Card
<1> If two PG option cards are connected, use both CN5-B and CN5-C. If only one PG option card is connected to the drive, use the CN5-C
connector.
<2> These option cards are not available for the application with Motor 2 Selection.
<3> These option cards are not available with models CIMR-A
4A0930 and 4A1200.
<4> When AI-A3 and DI-A3 are to be used as monitors, the card can be connected to any of CN5-A, CN5-B or CN5-C. The input status of
AI-A3 can then be viewed using U1-21, U1-22, and U1-23, and the input status of DI-A3 can then be viewed using U1-17.
Connector
Number of Cards Possible
PG-B3, PG-X3
CN5-C
2
<1>
PG-RT3
<2> <3>
, PG-F3
<2> <3>
CN5-C
1
DO-A3, AO-A3
CN5-A, B, C
1
SI-C3, SI-N3, SI-P3, SI-S3, SI-T3, SI-ET3,
AI-A3, DI-A3, SI-ES3, SI-B3, SI-M3,
SI-W3, SI-EM3, SI-EN3, SI-EP3, SI-ES3
<4>
CN5-A
1