6 DSP301 and DSP402 Specifications
YASKAWA ELECTRIC
SIEP C730600 64A 1000-Series Option SI-ES3 Technical Manual
23
CANopen DSP402 Event Description
The following state transitions are available in the CANopen DSP402 drive profile. Transition 0 and 1 are triggered at
start-up and when all start-up tests are performed, the option will be in state 3. Some commands like fault reset can be
triggered from more then one place. For example, the reset command can be triggered both from the bus with the
Controlword or from the application drive.
Table 12 Event description table
State Transition
Number
Transition Name
DSP402 Event
0
Startup
→
Not Ready To Switch On
Reset
1
Not ready to switch on
→
Switch on disabled
Self test and INIT successful
2
Switch on disabled
→
Ready to switch on
Shutdown command received
3
Ready to switch on
→
Switched on
Switch on command received
4
Switched on
→
Operation enabled
Enable operation command received
5
Operation enabled
→
Switched on
Disable operation command received
6
Switched on
→
Ready to switch on
Shutdown command received
7
Ready to switch on
→
Switch on disabled
Quick stop command received
8
Operation enabled
→
Ready to switch on
Shutdown command received
9
Operation enabled
→
Switch on disabled
Disable voltage command received
10
Switched on
→
Switch on disabled
Disable voltage or quick stop command received
11
Operation enabled
→
Quick stop active
Quick stop command received
12
Quick stop active
→
Switch on disabled
Quick stop completed or Disable voltage command received
13
All states
→
Fault reaction active
Fatal fault has occurred in the drive
14
Fault reaction active
→
Fault
Fault action is completed
15
Fault
→
Switch on disabled
Fault reset command received
16
Quick stop active
→
Operation enabled
Enable operation command received